Cockpit Air Conditioning and Pressurization

Parent Previous Next

Cockpit air conditioning and pressurization is by either of two systems: the ram-air system, or the liquid nitrogen air conditioning and pressurization system of the X-15 airplane.


The ram-air system, although it does not pressurize the cockpit and the No. 2 electronic equipment compartment, will furnish adequate cooling for these areas. Approximately 10 percent of the ram-air flow may be diverted to the cockpit by a cockpit control [11, fig. 5-3], with the remaining 90 percent being routed through a plenum, from which it is ducted to the No. 2 electronic equipment compartment. Flapper-type shutoff valves prevent the ram-air flow from entering the mixing chambers and blower ducts of the cooling system. The ram-air system must not be operated at the same time as the X-15 nitrogen system.


The X-15 liquid nitrogen system actually cools and pressurizes simultaneously. A vacuum-type contained in the No. 3 equipment compartment stores 176 pounds, or 26.5 gallons, of liquid nitrogen, which is depleted at a normal usage rate of approximately 5 pounds per minute. A pressure relief valve mounted in the nitrogen line between the top of the container and the nitrogen vent and build-up valve is preset to vent at 80 (+0, -4) psi.


Helium gas for pressurizing the X-15 liquid nitrogen tank is stored in a spherical tank in the No. 3 equipment compartment. Helium pressure is reduced from approximately 4200 psi at the tank to approximately 67 psi through a differential-pressure regulator. The helium gas is then routed into the top of the liquid nitrogen tank. The liquid nitrogen is forced out of the bottom of the tank and on through the system to the injectors. The liquid nitrogen is forced under pressure through the injectors into a stream of returning gaseous nitrogen within the mixing chambers, where it is mixed and recirculated.


The temperature of the air conditioning system is automatically controlled by the two thermostats that regulate the flow of nitrogen vapor from the liquid nitrogen injectors. The thermostats and the liquid nitrogen injectors are part of the system mixing chambers that connect with the plenum from which the regulated cooling gas is ducted to the electronic equipment requiring direct cooling.


The air conditioning and pressurization system includes an alternate system which automatically pressurizes the cockpit if component malfunctions result in loss of pressure. The alternate system includes a pressure switch, a solenoid-operated shutoff valve, two heat exchangers, and associated plumbing. When the alternate system is armed and the pressure switch contacts close (cockpit altitude rises above approximately 37,000 feet), the solenoid-operated shutoff valve is energized open. This allows liquid nitrogen to flow to a heat exchanger in each APU compartment. The nitrogen is converted to a gaseous state and expelled into the cockpit. The pressure switch contacts open when cockpit altitude drops below approximately 36,000 feet.


The augmented cooling system liquid nitrogen supply in the carrier airplane pylon is contained within a 6-cubic-foot tank. Approximately 292 pounds of liquid nitrogen is pressurized to approximately 63 psi by nitrogen pressure in the carrier airplane gaseous nitrogen system. Flow of the augmented cooling system liquid nitrogen to the X-15 is controlled from the launch operator's panel in the carrier airplane.



In this section:


Hazards of Gaseous and Liquid Nitrogen



See also:


Air Conditioning and Pressurization System Controls and Indicators

Operation of Air Conditioning and Pressurization System